Spray foam should be installed exactly as the product approval for that product says. Current approvals require a documented survey with a condensation risk assessment, timber below 19% or 20% moisture, the right underlay, usually a vapour control layer, protected cables and flues, a fire-resistant lining in habitable rooms and a trained installer[1][2].
Your next step:Compare your roof with what the approval requires
On this page
Key facts
- The BBA lists "automatically complies with Building Regulations" as a misconception about approved products (webinar, June 2021)[3]
- BBA product approval 23/7062 (2 January 2024) requires a documented survey with a condensation risk assessment before spraying[1]
- Timber moisture limit: below 20% (BBA 23/7062); substrate below 19% (Kiwa BAR-19-132 and BAR-20-170)[1][2][4]
- Government-commissioned modelling (February 2024) rated foam sprayed directly onto tiles or slates high risk in every scenario[5]
- The IMA Code of Practice (May 2023) sets no technical limits; those come from each product approval[6]
- Historic England (July 2024, revised February 2026): foam sprayed under a listed roof's covering needs listed building consent[7]
What does a spray foam product approval require?
A product approval is conditional: it assesses one product for particular roof build-ups and covers only the installation it describes, not whether your…
What conditions do the product approvals set?
Approvals differ by product, so the table shows typical conditions, not one rule for every foam: check the approval for your product.
Can spray foam be sprayed directly onto roof tiles, slates or felt?
Most current guidance says not: RICS says most products should not go directly onto tiles or slates, and government-commissioned modelling rated foam…
Does the industry Code of Practice set technical rules?
No: the Insulation Manufacturers Association (IMA) Code of Practice (May 2023) sets out a process and leaves the technical limits to each product approval.
Do Building Regulations apply to spray foam in a loft?
There is no single agreed answer in the sources: even the Building Safety Regulator's fire consultants wrote about the effects "if" applying foam counts as…
Can spray foam be used in a listed building?
Only with listed building consent, and Historic England says foam sprayed to the underside of the roof covering is "likely to harm the fabric of the…
Is spraying the rafters the only option?
No. For a loft not used as a room, RICS asks why insulate at rafter level when ceiling-level insulation costs less, and advises independent advice, separate…
What if your spray foam does not match the approval?
A mismatch means the installation is outside what the approval assessed; on its own it does not show what condition the roof is in.
What to do next
- Find the product approval number in your paperwork or the loft record, and ask for the full document for your product.
- Compare your roof with the approval: underlay, vapour control layer, ventilation, cables, flues, downlights and linings.
- If you are planning installation, ask building control in writing and get independent advice first.
- If the building is listed, ask your local council about listed building consent before any work.
- If you want independent evidence of what is in your loft, see the inspection below.
Compare your roof with what the approval requires
The approval's conditions cover the underlay, vapour control, ventilation, cables and linings. An independent inspection records the foam, what it is sprayed onto and the loft's condition, so you can compare them with what the approval requires.
Report within 48–72 hours of inspection. Independent: no installation, no removal, no referral commissions.
Travel included within about three hours of the North West; a fixed supplement further away, shown with your total before you book.
It records what can be seen and measured. It can't see timber under the foam, and it isn't a report for a lender.
Questions first? Call or WhatsApp 07349 718935 WhatsApp (opens in a new tab)
Case files like this
Anonymised inspections Jan has carried out. Every loft is different.
Holding a removal quote: the right foam, with ten departures from its product approval
Essex, London fringe · Recent inspection · Spray Foam Inspection
Open-cell foam from 2021 on a breathable membrane: the right product, over the area charged for. But its depth ran from nothing to about ten inches, both eaves were sealed, and the loft air held 3.8 g/kg more water than outside.
Read case file Installer ceased tradingInstaller ceased trading: a 25 mm air gap was designed and sold, but not reliably built
Leeds · Recent inspection · Spray Foam Inspection
Open-cell foam from 2024 on non-breathable felt; the installer has since ceased trading. It designed and sold a 25 mm ventilated gap behind the foam: at four visible points it measured 70, 32, 19 and 6 mm. The eaves were packed at fifteen points.
Read case file Selling a house with spray foamPlanning to sell: area matched the paperwork, foam depth up to twice the stated 100 mm
near Coventry · Recent inspection · Spray Foam Inspection
Open-cell foam from 2021 on felt. The area matched the paperwork; the depth did not: about 150–200 mm against 100 mm, with some rafters missed. All 12 timber readings were under 20%, the two highest at the ridge.
Read case fileGo deeper: the original sources
3 original documents, each with a note on what it covers.
Questions people ask
Does spray foam need building regulations approval?
The sources do not agree on one answer. The Building Regulations 2010 list no competent-person scheme for roof or loft insulation, the Planning Portal says loft insulation must meet the Approved Documents, and the regulator's fire consultants wrote about effects "if" foam counts as building work[18][19][17]. Ask your local building control in writing before work.
Can spray foam be applied directly to roof felt?
RICS says some products must not be applied to bitumen felt, and Product Sheet 1 of the current open-cell BBA approval traced for this guide covers breathable underlays only[14][1]. Government-commissioned modelling treated felt as high resistance and found open-cell foam without a vapour control layer high risk beneath it[5].
What moisture content should roof timbers be before spray foam?
It depends on the approval. BBA product approval 23/7062 requires timber below 20% by mass before spraying, and the Kiwa approvals traced for this guide set the substrate below 19% (one may not have been renewed)[1][2]. The industry Code of Practice sets no figure, so the approval for your product is the document to check[6].
Who is allowed to install spray foam insulation?
The approvals require installers trained and approved by the approval holder, and the industry Code says only manufacturer-trained and approved installers should apply products[1][6]. Approval bodies approve products, not installers[3]. Trading Standards guidance adds that an installer unfamiliar with the construction safety rules (CDM 2015) is a warning sign[8].