The UK Multifoil Guide · For professionals

    Multifoil: a reference for building control, surveyors, conveyancers and developers

    Last reviewed 26 November 2026 by Jan Pospisil, DEA qualified (ABBE Level 3)

    Reviewed weekly: every fact checked against the news and its sources. Page last updated 10 November 2026.

    Includes time-sensitive information: checked in the weekly sweep

    Independent: SprayFoamCheck doesn't install or remove insulation and takes no referral fees.

    Short answer

    This reference sets out declared values, calculation conventions, standards and dates for multifoil in England and Wales, each with its source. Under BR 443, multifoil U-values should rest on product data measured by a recognised test body; without it the default thermal resistance is 1.7 m²K/W, airspaces included.[1] Every worked example in the three BBA approvals opened includes other insulation.[2][3][4]

    Your next step:Get the foil checked independently

    On this page

    Key facts

    • BR 443 default with no correctly measured data: 1.7 m²K/W for the multi-foil and its adjacent airspaces together.[1]
    • Circular 06/2009: only hot-box or approved European assessment results carry a statutory presumption; building control may still weigh other evidence.[5]
    • Core thermal resistance in the approvals opened, with no air gaps: 0.91 to 3.58 m²K/W.[2][3][4][6]
    • Approved Document L 2026 takes effect in England on 24 March 2027; the Welsh 2026 editions on 4 March 2027.[7][8]
    • UKAS suspended the BBA on 26 February 2026. As of 10 November 2026 it was still suspended.[9][10]

    What is the short version for professionals?

    For Building Regulations, a multifoil roof's U-value is calculated and should rest on measured product data, and every worked example in the three BBA…

    Which standards and conventions apply, and what are their dates?

    Approved Document L 2026 (England) assesses U-values by BR 443, the BBA has its own conventions for reflective foil, and the test standard changed on 13…

    What values do the approvals opened declare?

    Core thermal resistance, with no air gaps, runs from 0.91 to 3.58 m²K/W across the four approvals we opened.

    Which conditions in the approvals affect a calculation or an inspection?

    The approvals opened set conditions on cavities, counter-battens, taped laps, ventilation above and other insulation.

    What are the building regulations dates for England and Wales?

    England's 2026 edition of Approved Document L takes effect on 24 March 2027, and the Welsh 2026 editions on 4 March 2027.

    What is the approval status, and how do you check it?

    The place to check is the issuing body's own register; for the BBA that is MyBBA Search, which asks users to sign up for an account.

    What have we not found, or not opened?

    We found nothing from a bank, building society, UK Finance or RICS that names foil or multifoil, as of 10 November 2026; UK Finance's handbook was not opened.

    How is this guide sourced and maintained?

    Each footnoted fact is traced to a source we opened; anything that can change carries its date.

    What to do next

    • Check the approval number and issue date on the issuing body's register.
    • Ask for the U-value calculation, and check the cavity depths, batten treatment and other insulation it assumes.
    • Check which edition of Approved Document L applies to the job's dates.
    Your next step

    Get the foil checked independently

    A Multifoil / Foil Inspection records what is fitted, how it is fixed and sealed, the air gaps and ventilation that can be seen, and moisture readings at the timbers that can be reached.

    Multifoil / Foil Insulation Inspection£295

    Report within 48–72 hours of inspection. Independent: no installation, no removal, no referral commissions.

    Travel included within about three hours of the North West; a fixed supplement further away, shown with your total before you book.

    It's evidence for your own decisions. It records what can be seen and measured, and says what is hidden.

    Questions first? Call or WhatsApp 07349 718935 WhatsApp (opens in a new tab)

    Not sure yet? Use the installation checklist

    Go deeper: the original sources

    3 original documents, each with a note on what it covers.

    Questions people ask

    How is a multifoil counted in a BR 443 U-value calculation?

    From measured product data: its core resistance plus surface emissivity, or a hot-box test with an airspace each side.[1] The BBA's January 2025 conventions add that the product's thickness counts as zero where battens squash it, unless a robust figure exists.[14]

    Does the air gap have to be 25 mm?

    Not in the approvals we opened: they count a roof cavity from 13 mm and a wall cavity from 20 mm.[2][3][4] A common claim is that the BBA requires 25 mm; that is the depth at which BR 443's default airspace values apply.[1]

    Does England's Approved Document L 2026 require a BBA approval for multifoil?

    We found no such rule. In the parts of the 2026 edition we read, about two thirds, there is no mention of multi-foil or reflective insulation, and no rule requiring a BBA document.[13] Paragraph 3.1 says U-values are assessed by BR 443.[13]