The multifoil problems in our sources come from how it was sold and fitted: performance claims that lab tests do not support, missing air gaps, battens or taped joints, and use over a cold loft, which none of the under-rafter product approvals opened covers.[1][2][3][4] Not every installation is a problem. We hold no figures on how often faults occur.
On this page
Key facts
- One BBA approval says additional insulation "will be required"; every worked example in all three includes other insulation.[2][3][4]
- Under BR 443, a foil surface adds thermal resistance only when it faces an airspace. Against another surface it adds nothing.[5]
- Where the underlay has high vapour resistance, two approvals say the space under it should be ventilated.[2][4]
- None of the under-rafter approvals opened covers a cold loft insulated at ceiling level.[2][3][4]
- In April 2008, LABC knew of no multi-foil that met a roof U-value of 0.2 W/m²K as a single layer.[1]
- A Cornwall energy charity's page, which carries a Cornwall Council Trading Standards warning, says adding foil to a loft is not recommended (page undated).[6]
What problems do people have with multifoil?
The problems we can source are about how multifoil was sold, where it was used and how it was fitted.
What if it was sold as more than it is?
Then the claim you were given may rest on comparison tests in paired buildings, not on laboratory values.
What if it was fitted without the air gaps or battens?
Then the foil face on that side adds nothing: under BR 443, the conventions used for U-value calculations, a foil surface adds thermal resistance only when…
What if the joints and eaves were not sealed?
Then the multifoil is not acting as a vapour control layer (a layer that holds back water vapour): each under-rafter product in the approvals we opened acts…
Does multifoil cause condensation after fitting?
It depends on the roof around it: the approvals we opened treat the risk of condensation inside the roof as acceptable where the roof is designed to BS…
What if it was fitted over a cold loft?
Then it is in a place that none of the four approvals we opened addresses.
What if it was fitted after spray foam removal?
Then the same approval conditions apply as for any other installation: if the foam is removed and multifoil is fitted at rafter level, the BBA approvals'…
What if the paperwork does not match the product?
Then the approval quoted in your paperwork may not describe what is in the roof, because each approval's figures and fitting rules belong to named products.
What do the product approvals require?
In short, between them they require the right position, sealed joints, an air gap, ventilation above where it is needed, extra insulation and distance from heat.
Can multifoil be put right or taken out?
We do not know from published sources.
How do I find out which applies to me?
Start with two questions: where the foil is, and what the paperwork says it is.
Answer up to four questions to find the right page. Nothing you enter is sent anywhere.
Step 1 of 4
What best describes your situation?
- Where is it? A sloping ceiling that encloses a habitable space is the use two BBA approvals describe.[2][4] None of the four addresses a cold loft.[2][3][4][10]
- What is it? Find the product name and the approval number on the contract or invoice, and compare them with what was fitted.
- What can be seen? Where the multifoil is still visible, look for tape along every lap, battens over the foil and sealed eaves.[2][3]
An independent inspection records what can be seen and measured, and says what is hidden. It gives you independent evidence for your own decision.
What to do next
- Find the contract, the invoice and any product approval they name.
- Note where the foil is: behind a sloping ceiling with a room below, or under the rafters of a cold loft.
- Do not agree to removal or replacement on the doorstep or over the phone.
- If something does not match, have it recorded independently before anything is changed.
Get the foil checked independently
A Multifoil / Foil Inspection records what is fitted, how it is fixed and sealed, the air gaps and ventilation that can be seen, and moisture readings at the timbers that can be reached.
Report within 48–72 hours of inspection. Independent: no installation, no removal, no referral commissions.
Travel included within about three hours of the North West; a fixed supplement further away, shown with your total before you book.
It's evidence for your own decisions. It records what can be seen and measured, and says what is hidden.
Questions first? Call or WhatsApp 07349 718935 WhatsApp (opens in a new tab)
Case files like this
Anonymised inspections Jan has carried out. Every loft is different.
See all case filesGo deeper: the original sources
3 original documents, each with a note on what it covers.
Questions people ask
How often do multifoil problems happen?
We do not know. We found no published count or percentage for any multifoil fault, as of 10 November 2026. What we hold are the conditions in the product approvals, a 2008 LABC guidance note, and a Cornwall energy charity's page, quoting Cornwall Council Trading Standards, which is undated.[2][1][6] None of these measures how common a fault is.
Are there problems with multi-foil loft insulation over a cold loft?
None of the four product approvals we opened addresses a cold loft or insulation at loft-floor level.[2][3][4][10] A Cornwall energy charity's page, which carries a Cornwall Council Trading Standards warning, says adding foil to a loft is not recommended and gives little benefit there; the page is undated.[6]
Is my multifoil's BBA approval still valid?
UKAS suspended the BBA on 26 February 2026.[13] On 15 June 2026 it said existing approvals remain valid until they expire, that no new ones are issued under UKAS during the suspension, and that the suspension's latest end date is 25 November 2026.[13] As of 10 November 2026, that statement was unchanged and the BBA's home page still said the suspension was in place.[13][14] We have not checked any approval against the BBA's own register.
Does multifoil have to come out?
Not necessarily: removal is not presumed to be needed. We found no published guidance on removing or replacing multifoil, as of 10 November 2026. Whether anything should change depends on what was fitted, where, and whether it matches its product approval, with its taped laps, counter-battens and other insulation.[2][3][4]